Quest Controls BACnet T-Stat Spécifications Page 14

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 13
BACnetTStatUser’sManualRev1.1,7/28/11 Page|13
7.0CareandCleaning
TheBACnetTStatshouldprovideyearsofuninterruptedservice.Minimalpreventivemaintenanceis
required.However;itisimportanttomakesurethattheT
Statiskeptfreeofdust.AdustyTStatwillnotallowairto
circulateproperlyaroundthebuiltintemperatur e sensor
effectingproperoperation
oftheunit.
8.0Troubleshooting
LCDScreenisdarkandnocharactersare
displayed
Removecoverandverifypresenceofpoweronthe“R”
terminal,checkconnectionofthecommononthe“C”
terminal.Checkforpresenceof24VACbetweenRandC.
TStatmodesayCool1,butcompressor
doesnotengage
VerifyconnectiontoHVACunit.Ensureshortcycletimeris
notinhibitingunit.
Clocklosestimeafterpowerfailure ReplacetheCR1025Lithiumbattery
Buttonsdonotrespond Pressbuttonsslowly,somefunctionsmaytakepressingthe
buttontwice.
Displayiscorrupted First,cyclepowertotheunit.Ifthisdoesnotcorrectthe
problem,resetsystembyremovingtheTStatbodyfromthe
mountingplate.Thenreturnthebodytothemountingplate
whiledepressingtheuparrow,centerbutton anddown
arrowallatthesametime.
Thedisplaywillrespondwith
“ColdSense”,thesebuttonsmustbehel dforaminimum5
second.Thiswillbegina
systemrestartandthe
displaywillrespondwith
“ColdStart”.Releasethebuttonsatthistime.Thisaction
willresettheTStatandreturnallsettingstotheir
factory
defaults.Allcustomscheduleswillbeerased.
Vue de la page 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 27 28

Commentaires sur ces manuels

Pas de commentaire