Quest Controls BACnet T-Stat Manuel de service Page 263

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 360
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 262
I/O Modules • 263
Process Data Architecture for MODBUS/TCP
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
Input Process Image
Byte Destination
Offset
High Byte Low Byte
Remark
0 - S Status byte
1 D1 D0
2 D3 D2
Counter Value
Output Process Image
Byte Destination
Offset
High Byte Low Byte
Remark
0 - C Control byte
1 D1 D0
2 D3 D2
Counter Setting Value
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the In-
put and Output Process Image (4 bytes of counter data and 1 byte of con-
trol/status). The two counter values are supplied as 16 bits. The following ta-
bles illustrate the Input and Output Process Image, which has a total of 3
words mapped into each image. Word alignment is applied.
Input Process Image
Byte Destination
Offset
High Byte Low Byte
Remark
0 - S Status byte
1 D1 D0 Counter Value of Counter 1
2 D3 D2 Counter Value of Counter 2
Output Process Image
Byte Destination
Offset
High Byte Low Byte
Remark
0 - C Control byte
1 D1 D0 Counter Setting Value of Counter 1
2 D3 D2 Counter Setting Value of Counter 2
Vue de la page 262
1 2 ... 258 259 260 261 262 263 264 265 266 267 268 ... 359 360

Commentaires sur ces manuels

Pas de commentaire